CGMYY - 0630-00002 LEAD/ACID BATTERY (TELEDYNE BATT,GILL (SUPPLEM))

Product Identification

Product ID:0630-00002 LEAD/ACID BATTERY (TELEDYNE BATT,GILL (SUPPLEM))
MSDS Date:02/01/1997
FSC:6140
NIIN:01-356-5925
Kit Part:Y
MSDS Number: CGMYY

Responsible Party
TELEDYNE BATTER PRODUCTS, TELEDYNE INC COMPANY
840 W BROCKTON AVE
REDLANDS, CA 92373
US

Emergency Phone: 800-535-5053

Info Phone: 714-793-3131

Preparer: ROBIN J. FRIED

Cage: 84375

Contractor
TELEDYNE BATTER PRODUCTS, TELEDYNE INC COMPANY
431 REDLANDS, CA 92373 US

Telephone: 909-793-3131

Cage: 84375

Ingredients

LEAD (SARA 313) (CERCLA) AND LEAD COMPOUNDS

CAS: 7439-92-1

RTECS: OF7525000

Fraction By Weight: <94%

OSHA PEL SEE 1910.1025

ACGIH TLV: 0.05MG/M3, A3; 9596

EPA Report Quantity: 1 LB

DOT Report Quantity: 1 LB


SULFURIC ACID (SARA 302/313) (CERCLA) (ELECTROLYTE)

CAS: 7664-93-9

RTECS: WS5600000

Fraction By Weight: <58%

OSHA PEL 1 MG/M3

ACGIH TLV: 1 MG/M3/3 STEL; 9596

EPA Report Quantity: 1000 LBS

DOT Report Quantity: 1000 LBS


ANTIMONY (SARA 313) (CERCLA)

CAS: 7440-36-0

RTECS: CC4025000

Fraction By Weight: <0.4%

OSHA PEL 0.5 MG/M3

ACGIH TLV: 0.5 MG (SB)/M3; 9596

EPA Report Quantity: 5000 LBS

DOT Report Quantity: 5000 LBS


ARSENIC (SARA 313) (CERCLA)

CAS: 7440-38-2

RTECS: CG0525000

Fraction By Weight: <0.1%

OSHA PEL SEE 1910.1018

ACGIH TLV: 0.01 MG/M3, A1; 9596

EPA Report Quantity: 1 LB

DOT Report Quantity: 1 LB


BARIUM SULFATE

CAS: 7727-43-7

RTECS: CR0600000

Fraction By Weight: <0.4%

OSHA PEL 15 MG/M3 TDUST

ACGIH TLV: 10 MG/M3 TDUST; 9596


CALCIUM COMPOUNDS

CAS: 7440-70-2

RTECS: EV8040000

Fraction By Weight: <0.2%


CARBON BLACK EXTRACTS

CAS: 1333-86-4

RTECS: FF5800000

Fraction By Weight: <0.1%

OSHA PEL 3.5 MG/M3

ACGIH TLV: 3.5 MG/M3; 9596


NICKEL SULFATE (SARA 313) (CERCLA)

CAS: 7786-81-4

RTECS: QR9350000

Fraction By Weight: <0.1%

OSHA PEL 1 MG(NI)/M3

ACGIH TLV: 0.1 MG(NI)/M3; 9596

EPA Report Quantity: 100 LBS

DOT Report Quantity: 100 LBS


TIN COMPOUNDS

CAS: 7440-31-5

RTECS: XP7320000

Fraction By Weight: <0.3%

OSHA PEL 2 MG/M3

ACGIH TLV: 2 MG/M3; 9596

Hazards

LD50 LC50 Mixture:NONE SPECIFIED BY MANUFACTURER.
Routes of Entry: Inhalation:YES Skin:YES Ingestion:YES
Reports of Carcinogenicity:NTP:YES IARC:YES OSHA:YES
Health Hazards Acute and Chronic:INHAL:ACID-BURN RESP TRACT,LUNG
IRRIT,PULM EDEMA.PB-ABSORB BY RESP SYS ACUTE/CHRON RESP
IRRIT.SKIN:ACID-BURN/LOC IRRIT.PB-ABSORB THRU
SKIN.EYE:ACID-IRRIT,CORNEAL BURN,CONJ,BLIND,SEVERE,PERM INJURY.PB-
IRRIT.INGEST:ACID-BURN MOUTH/ESOPHA/STOM.PB-ABSORB BY RESP
SYS,ACUTE/CHRON OVEREXPO.UNDER NORM COND HAZ MATL NOT RELEASE
Explanation of Carcinogenicity:PER
MSDS:LEAD-IARC/OSHA;ARSENIC-IARC/OSHA;SULFURIC ACID-IARC.
Effects of Overexposure:ACUTE:ACID-IRRIT EYE/NOSE/THROAT.DIFFI
BREATH,EYE/SKIN BURNS/IRRIT.LB-WEAK,VOMIT,LOSS OF APPETITE,UNCOORD
BODY MOVEMENTS,CONVULS,STUPOR,COMA.CHRONIC:ACID-IRRIT SKIN.EROSION
OF TEETH,IRRIT EYE,CHRONIC INFLAMM NOSE/THROAT/BORNCHIAL
TUBES.PB-WEAK,INSOMNIA,HYPERTENSION,SLGITH IRRIT SKIN/EYE,METALLIC
TASTE,ANEMIA,(SUPPPLE)
Medical Cond Aggravated by Exposure:NONE SPECIFIED BY MANUFACTURER.

First Aid

First Aid:EYE:WASH IMMED W/LG AMTS OF H2O LIFTING LIDS CONT.GET MED
ATTN.SKIN:IMMED FLUSH AREA W/LG AMTS OF H2O.REMOVE CONTAM CLOTH.GET
MED ATTN.INHAL:REMOVE FROM AREA.BREATH STOP PERFORM CPR.GET IMMED
MED ATTN .INGEST:ACID-GIVE EMPLOYEE LG AMTS OF H2O IF
CONSCIOUS.DONT INDUCE VOMIT.GET MED ATTN.PB-GET IMMED MED ATTN.

Fire Fighting

Flash Point:NA
Autoignition Temp:Autoignition Temp Text:NA
Lower Limits:NA
Upper Limits:NA
Extinguishing Media:USE DRY CHEMICAL EXTINGUISHER,BATTERY CASE WILL
BURN.
Fire Fighting Procedures:USE OF WATER IN EXTINGUISHING BURNING BATT MAY
CAUSE SPATTERING DUE TO PRESENCE OF MOLTEN LEAD.
Unusual Fire/Explosion Hazard:WHILE BATT BEING CHARGED HYDROGEN GAS IS
PRODUCED.BATT MAY EXPLODE IF HYDROGEN GAS IS TRAPPED INSIDE BATT
CASE.KEEP IGNITION SOURCES AWAY.

Accidental Release

Spill Release Procedures:SHOULD BATT BREAK/OPN ISOLATE AREA.ABSORB
ELECTROLYTE W/NON-ORG TYPE ABSORBENT(DRY SAND,EARTH).AVOID DIL
W/H2O.PB SPILL SHOULD BE HEPA VACUUM/WET MOP.DONT DRY SWEEP OR USE
COMPRESSED AIR.PREVENT LEAD DUST FROM BECOMING AIRBORNE.USE PPE.
Neutralizing Agent:USE SODA ASH OR BAKING SODA TO NEUTRALIZE
ELECTROLYTE.

Handling

Handling and Storage Precautions:UNDER NORMAL CONDITIONS OR USE EXPO TO
PB DOESNT OCCUR.AVOID USE OF UNINSULATED TOOLS.IF REQUIRE TAKE CARE
NOT TO MAKE CONNECTION BETWEEN 2BATT(OTHPR)
Other Precautions:CONT:TERMINALS AS SEVERE SPARKING MAY OCCUR WHICH
COULD RESULT IN EXPLO.RING/METAL WATCH BANDS REMOVE WHILE SERVICING
BATT.PROVIDE SUFF VENTI-PREVENT DANGEROUS GAS BUILDUP.BATT RM AIR
CONDITION PART O F OVERALL BLDG EXHAU SYS TO OUTSIDE.

Exposure Controls

Respiratory Protection:UNDER NORMAL CONDITIONS OF USE RESPIRATORY
PROTECTION IS NOT REQUIRED.HOWEVER SHOULD CONDITIONS ARISE WHERE
RESPIRATORS ARE NEEDED USE ONLY NIOSH/MSHA RESPIRATORS APPROVED FOR
DUST/FUME/MIST.
Ventilation:BATT CHARGE AREA MUST BE ADEQU VENTI-PREVENT HAZ FLAMM
GAS/ACID MIST CONC.DESIGN CRITERIA FOR VENTI SYS-INDUST MAN ACGIH
Protective Gloves:GLOVES APPROV FOR SULFURIC ACID
Eye Protection:CHEM GOGG,FULL FACE SHIELD
Other Protective Equipment:ACID RESISTANT APRON.
Work Hygienic Practices:H2(LIGHTER THAN
AIR,COLORLESS,ODORLESS,TASTELESS,DIFF DETECT)/O2 PRODUCE DURING
NORM BATT OPERATION ESPEC DURING CHARGIN
Supplemental Safety and Health
AIRCRAFT BATT,CENTRURION,BIG BEAM,TELSTAR,SILTRON,AIR
TRACTOR,SCHWIEZER. PHY DATA FOR LEAD.
OVEREXPO:CONSTIPATION,HEAD,MUSCLE,JT PAINS,NEUTROMUSCULAR
DYSFUNCT,PARALYSIS,PNEUMOCONIOSIS.PB-IMPAIR REPROD SYS,DMG
KID,HEMATOPOIETIC &/OR CNS.

Chemical Properties

HCC:N1
Boiling Pt:B.P. Text:3164F,1740C
Melt/Freeze Pt:M.P/F.P Text:621F,327C
Decomp Temp:Decomp Text:NP
Vapor Pres:NA
Vapor Density:NA
Spec Gravity:11.3 LEAD
pH:NP
Viscosity:NP
Evaporation Rate & Reference:NA PB;<1 ELECTROLYTE
Solubility in Water:NA PB;100% ELECTROLY
Appearance and Odor:NO ODOR,BATT CASE-PINK,WHITE,OLIVE
GREEN,BLACK.ELECTROLYTE-CLEAR LIQ.MFG ARTICL
Percent Volatiles by Volume:NA
Corrosion Rate:NP

Stability

Stability Indicator/Materials to Avoid:YES
CONTACT OF ELECTROLYTE W/ORGANIC MATL.ALSO CONTACT OF LEAD W/STRONG
OXIDIZERS MAY LIBERATE HYDROGEN GAS.
Stability Condition to Avoid:NONE SPECIFIED BY MANUFACTURER.
Hazardous Decomposition Products:SULFURIC ACID MIST,SULFUR DIOXIDE AND
CARBON MONOXIDE MAY BE RELEASED WHEN ELECTROLYTE DECOMPOSES

Disposal

Waste Disposal Methods:ELECTROLYTE/SCRAP BATT REGUL WASATE.SCRAP BATT
CONTAIN MATL WHICH ARE RECYCLABLE.MUST BE RETURNED TO AUTHORIZED
RECYCLER.ELECTROLYTE SHOULD BE HAULED TO PERMITT TREAT
FAC.PROPOSITION 65.SARA TITLE III CHEMS.

Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.